Tankless Water Heater Sizing Chart
A GPM figure without a temperature rise is not a specification. Here is how to do it properly.
Heat & Tap earns a commission on qualifying purchases made through the Amazon links on this page, at no extra cost to you. Commission does not decide what we recommend or how we rank it. Full disclosure.

Size a tankless unit on two numbers: simultaneous flow in GPM, and your temperature rise. Rise is your target temperature minus your winter inlet temperature. Two showers in a cold-inlet climate needs about 5 GPM at a 70°F rise — which is a 199,000 BTU gas unit, not a 24 kW electric one.
Every tankless listing leads with a maximum GPM figure, and that figure is almost always measured at a small temperature rise. A unit advertised at 9.5 GPM may deliver 5.5 GPM at the rise your house actually needs in February. Both numbers are real. Only one is useful to you.
Step 1: your temperature rise
Rise = target outlet temperature minus inlet temperature. Most households want 120°F at the tap. Inlet temperature is groundwater temperature, and it varies hugely by latitude and by season.
| Region | Winter inlet, approximate | Rise needed |
|---|---|---|
| South Florida, south Texas, Hawaii | 68 to 72°F | 48 to 52°F |
| Gulf coast, southern California, Arizona | 60 to 68°F | 52 to 60°F |
| Mid-Atlantic, Carolinas, Tennessee | 50 to 58°F | 62 to 70°F |
| Pacific Northwest, Ohio valley, Missouri | 45 to 52°F | 68 to 75°F |
| Upper Midwest, New England, Mountain West | 38 to 45°F | 75 to 82°F |
These are planning figures, not measurements of your street. If you want the real number, run the cold tap for two minutes in January and put a thermometer in the stream. That five-minute exercise is more accurate than any chart.
Step 2: your simultaneous flow
| Fixture | Flow | Notes |
|---|---|---|
| Shower, modern head | 1.5 to 1.8 GPM | WaterSense heads are 2.0 GPM or less |
| Shower, older head | 2.2 to 2.5 GPM | Pre-1992 heads can be higher still |
| Bathroom faucet | 0.5 to 1.5 GPM | Aerated faucets are at the low end |
| Kitchen faucet | 1.5 to 2.2 GPM | |
| Dishwasher | 1.0 to 2.5 GPM | Many modern units heat their own water |
| Washing machine | 1.5 to 3.0 GPM | Only on a hot or warm cycle |
| Tub filler | 4.0 to 8.0 GPM | A tub filler alone can exceed a unit's output |
Add up the fixtures that will genuinely run at the same time. Not every fixture in the house — the ones that overlap on a real morning. Most households are honest at two showers plus a sink.
Step 3: the chart
| What runs at once | Warm inlet (50F rise) | Moderate (65F rise) | Cold inlet (75F+ rise) |
|---|---|---|---|
| 1 shower | 1.8 GPM | 1.8 GPM | 1.8 GPM |
| 1 shower + 1 sink | 2.8 GPM | 2.8 GPM | 2.8 GPM |
| 2 showers | 3.6 GPM | 3.6 GPM | 3.6 GPM |
| 2 showers + 1 sink | 4.6 GPM | 4.6 GPM | 4.6 GPM |
| 3 showers | 5.4 GPM | 5.4 GPM | 5.4 GPM |
| Unit class needed | Electric 24 kW or gas 150k BTU | Gas 180k to 199k BTU | Gas 199k BTU |
The GPM requirement does not change with climate — the shower uses the same water. What changes is which unit can deliver it. That is the whole point, and it is why the bottom row is the row that matters.
Real published rise-versus-flow data
Stiebel Eltron publishes a full rise-versus-flow table for the Tempra Plus, which makes it the easiest unit in this category to size honestly. Here it is at both supply voltages:
| Flow | Rise at 240 V (24 kW) | Rise at 208 V (18 kW) |
|---|---|---|
| 1.50 GPM | 92°F | 82°F |
| 2.25 GPM | 73°F | 54°F |
| 3.00 GPM | 54°F | 41°F |
| 4.50 GPM | 37°F | 27°F |
On the gas side, Rheem publishes 5.5 GPM at a 70°F rise for the RTGH-95DVLN against a 9.5 GPM maximum at a 35°F rise. Same unit, same day, nearly double the flow — because the second figure is measured at half the rise. When you compare tankless units, compare them at the same rise or you are not comparing anything.
Quick picks
Tap any row to read the full assessment below, or go straight to Amazon from the right-hand column. We earn a commission on qualifying purchases at no extra cost to you.
| # | Product | Best for | Price |
|---|---|---|---|
| 1 | ![]() Rheem Prestige RTGH-95DVLNThe condensing gas tankless most houses should start with: 5.5 GPM at a 70°F rise covers two showers in a cold-inlet climate, and the 12-year residential heat exchanger warranty is the longest on this list. | Most whole-house gas jobs | Check price on Amazon No live price feed on this site, so we show none. #ad |
| 2 | ![]() Stiebel Eltron Tempra 24 PlusThe electric tankless to buy if you are going to buy one at all: it publishes its full rise-versus-flow curve, and the Advanced Flow Control throttles flow instead of letting the temperature sag. | Whole-house electric, warm inlet | Check price on Amazon No live price feed on this site, so we show none. #ad |
| 3 | ![]() EcoSmart ECO 27The biggest electric unit most homes can actually feed: 27 kW across three 40 A breakers, 6.6 GPM maximum, and a lifetime limited warranty on the unit. | Maximum electric output | Check price on Amazon No live price feed on this site, so we show none. #ad |
Units with honest published figures

Pick 1 — Most whole-house gas jobs
Rheem Prestige RTGH-95DVLN
The condensing gas tankless most houses should start with: 5.5 GPM at a 70°F rise covers two showers in a cold-inlet climate, and the 12-year residential heat exchanger warranty is the longest on this list.
| Fuel | Natural gas (LP variant sold separately) |
|---|---|
| Gas input | Up to 199,900 BTU/h |
| Flow at a 70°F rise | 5.5 GPM |
| Maximum flow | 9.5 GPM at a 35°F rise |
| Efficiency | Up to 0.93 UEF, stainless condensing heat exchanger |
| Minimum activation flow | 0.4 GPM |
| Venting | Up to 150 ft of 3-inch PVC; 60 ft of 2-inch PVC |
| Dimensions | 18-1/2 in W x 9-3/4 in D x 27-1/2 in H |
| Warranty | 12-year heat exchanger (residential), 5-year parts, 1-year labor |
What is good
- The 70°F-rise figure is published, so you can size it honestly instead of guessing from the headline number
- Condensing design vents in PVC, which is far cheaper to run than stainless category III pipe
- 0.4 GPM activation means a trickle at a bathroom faucet still fires the burner
- Long PVC vent runs let you put it where the gas line already is
What is not
- Needs a gas line sized for nearly 200,000 BTU/h — many existing 1/2-inch runs are not
- Condensate has to go somewhere, which means a drain or a condensate pump
- Annual descaling is not optional on hard water
Skip it if: Skip it if your gas meter and line cannot carry 199,900 BTU/h. Upsizing the gas line is often the single largest cost in a tankless conversion, and no amount of unit quality fixes a starved burner.
No live price feed on this site, so we show none. #ad
Specifications above from Rheem RTGH series specification sheet (PDF); Pace Supply listing, RTGH-95DVLN, 199 kBtu/hr. We have not tested this unit ourselves.

Pick 2 — Whole-house electric, warm inlet
Stiebel Eltron Tempra 24 Plus
The electric tankless to buy if you are going to buy one at all: it publishes its full rise-versus-flow curve, and the Advanced Flow Control throttles flow instead of letting the temperature sag.
| Output at 240 V | 24 kW |
|---|---|
| Output at 208 V | 18 kW |
| Breakers | 2 x 50 A double-pole |
| Wire | 2 x 6 AWG copper |
| Current draw | 100 A |
| Minimum electrical service | 150 A |
| Rise at 240 V | 54°F at 3.0 GPM; 73°F at 2.25 GPM; 37°F at 4.5 GPM |
| Rise at 208 V | 41°F at 3.0 GPM; 54°F at 2.25 GPM; 27°F at 4.5 GPM |
| Maximum flow | 8 GPM |
What is good
- Publishes rise at four flow rates on both voltages, which is the only honest way to size an electric tankless
- Advanced Flow Control cuts flow to hold the set temperature rather than delivering lukewarm water
- No venting, no gas line, no condensate
- Small enough to go in the cabinet it replaced
What is not
- 100 A of draw and a 150 A minimum service rules out a lot of older houses
- At 208 V it loses a quarter of its output, and plenty of homes are nearer 208 than 240
- Running cost follows the electric rate, which is usually worse than gas per BTU
Skip it if: Skip it if your inlet water drops to 45°F in winter and you want two showers at once. At a 73°F rise it delivers 2.25 GPM — one shower, nothing else. Cold-inlet climates are where electric tankless disappoints people.
No live price feed on this site, so we show none. #ad
Specifications above from Stiebel Eltron Tempra Plus technical specifications (PDF); Stiebel Eltron Tempra Plus submittal sheet (PDF). We have not tested this unit ourselves.

Pick 3 — Maximum electric output
EcoSmart ECO 27
The biggest electric unit most homes can actually feed: 27 kW across three 40 A breakers, 6.6 GPM maximum, and a lifetime limited warranty on the unit.
| Output | 27 kW at 240 V, single phase |
|---|---|
| Current draw | 113 A |
| Breakers | 3 x 40 A |
| Wire | 3 x 8 AWG |
| Maximum flow | 6.6 GPM |
| Minimum activation flow | 0.3 GPM |
| Dimensions | 17 in x 17 in x 3-5/8 in |
| Weight | 14.7 lb |
| Connections | 3/4 in NPT |
| Warranty | Lifetime limited |
What is good
- Highest output of any single electric unit here, so it holds temperature at higher flow
- Lifetime limited warranty on the unit is unusual at any price
- 3-5/8 inches deep — it genuinely disappears on a wall
- 0.3 GPM activation flow is the lowest on this page
What is not
- 113 A of draw needs three circuits and, in practice, a 200 A service
- The published flow is a maximum, not a rise-qualified figure — you have to do the rise math yourself
- No buffer, so a sudden flow change is felt at the shower head
Skip it if: Skip it if your panel is 100 A or 125 A. Three 40 A circuits and 113 A of draw is a service upgrade, and a service upgrade usually costs more than the entire water heater.
No live price feed on this site, so we show none. #ad
Specifications above from EcoSmart ECO 27 technical data (BIMobject). We have not tested this unit ourselves.
The electric service problem
Electric tankless sizing runs into the panel before it runs into the water. The real numbers from manufacturer documentation:
- Stiebel Eltron Tempra 24 Plus — two 50 A double-pole breakers, two runs of 6 AWG copper, 100 A of draw, minimum 150 A service.
- EcoSmart ECO 27 — three 40 A breakers, three runs of 8 AWG, 113 A of draw.
- Rheem RTEX-24 — three 40 A breakers and a 200 A service requirement.
- EcoSmart ECO 11 — one 60 A breaker, 6 AWG, 54 A of draw. This is the one that fits an existing panel, and it is a single-fixture unit.
If your house has a 100 A or 125 A service, whole-house electric tankless is a service upgrade before it is a water heater, and a service upgrade usually costs more than the entire appliance. Breaker and wire size has the detail.
What goes in with it
A water heater is a system, not a box. These are the parts that go in with it, and the ones people discover they need halfway through the job.
- Flush kit
The annual descale is not optional on a tankless unit, and you need a pump, hoses and a bucket.
- Descaler solution
What actually dissolves the scale once the kit is hooked up.
- Recirculation pump
Fixes the cold-water delay that makes new tankless owners call a plumber.